5.5 Auxiliary function setting mode 2
Character
Name, Description, Setting range
Default
Input type
• With multi-range input, 5 thermocouple and 4 RTD input types and
unit (
or
) can be selected
.
• With TC multi-range input, 5 thermocouple input types and unit (
or
) can be selected.
• With TC K input, 2 ranges and unit (
or
) are selectable.
K
[TC multi-range input]
: K
0 to 1370
: J
0 to 1000
: PL-
0 to 1390
: N
0 to 1300
: E
0 to 800
: K
0 to 2500
: J
0 to 1800
: PL-
0 to 2500
: N
0 to 2300
: E
0 to 1500
[Multi-range input]
: K
0 to 1370
: J
0 to 1000
: PL-
0 to 1390
: N
0 to 1300
: E
0 to 800
: Pt100
-199.9 to 850.0
: JPt100 -199.9 to 500.0
: Pt100
-200 to 850
: JPt100 -200 to 500
: K
0 to 2500
: J
0 to 1800
: PL-
0 to 2500
: N
0 to 2300
: E
0 to 1500
: Pt100
-199.9 to 999.9
: JPt100 -199.9 to 900.0
: Pt100
-300 to 1500
: JPt100
-300 to 900
[TC K input]
: K
0 to 400
: K
0.0 to 400.0
: K
0 to 750
: K
0.0 to 750.0
PV filter time constant
• Sets PV filter time constant value.
If the value is set too large, it affects control result due to
the delay of response.
• Setting range: 0.0 to 10.0 seconds.
0.0sec
OUT high limit
• Sets control output (OUT) high limit value.
• Not available for the ON/OFF action.
• Setting range: OUT low limit to 100%
DC current output type: OUT low limit to 105%)
100%
OUT low limit
• Sets control output (OUT) low limit value.
• Not available for the ON/OFF action.
• Setting range: 0% to OUT high limit
DC current output type: -5% to OUT high limit)
0%
Output ON/OFF action hysteresis
• Sets ON/OFF action hysteresis of control output (OUT).
• Available only for the ON/OFF action.
• Setting range: 0.1 to 100.0
1.0
Event output function
• Selects Alarm, Loop break alarm or Heater burnout alarm output as
an Event output function.
• Not available for the FCL-130.
• Heater burnout alarm is selectable only when [W] option is added.
•
: Alarm
: Loop break alarm
: Heater burnout alarm (W option)