20
10. Specifications
10.1 Standard specifications
Mounting
: Flush
Setting
: Input system using membrane sheet key
Display
PV/SV display
: Red LED display 4 digits, size, 8(H) x 4(W)mm
Accuracy (Setting, indication)
Thermocouple
: Within
0.3% of each input span 1 digit,
or 2
(4 ), whichever is greater
RTD
: Within
0.2% of each input span 1 digit
Input range
[Multi-range input], [TC multi-range input]:
K
: 0 to 1370
(0 to 2500 )
J
: 0 to 1000
(0 to 1800 )
E
: 0 to
800
(0 to 1500 )
PL-
: 0 to 1390
(0 to 2500 )
N
: 0 to 1300
(0 to 2300 )
*
Pt100 : -199.9 to 850.0
(-199.9 to 999.9 ), -200 to 850
(-300 to 1500 )
*
JPt100: -199.9 to 500.0
(-199.9 to 900.0 ), -200 to 500
(-300 to 900 )
* Pt100 and JPt100 are not included in TC multi-range input type.
[TC K input]:
K
: 0 to 400
(0 to 750 )
0.0 to 400.0
(0.0 to 750.0 )
Input sampling period
: 0.25 seconds
Input
Thermocouple
: K, J, E, PL- , N
External resistance: 100
or less
When input is burnt out: Overscale
RTD
: Pt100, JPt100, 3-wire system
Allowable input lead wire resistance: 10
or less per wire
When input is burnt out: Overscale
Control output (OUT)
Relay contact
: 1a
Control capacity,
3A 250V AC (resistive load)
1A 250V AC (inductive load cos =0.4)
Non-contact voltage: For SSR drive
12
+2
0
V DC, Maximum 40mA (short circuit protected)
DC current
: 4 to 20mA DC
Load resistance, maximum 550
Supply voltage
: 100 to 240V AC, 50/60Hz, 24V AC/DC, 50/60Hz
Allowable voltage fluctuation
:
100 to 240V AC: 85 to 264V AC
24V AC/DC
: 20 to 28V AC/DC
A
larm output
When alarm action is set as Energized, the alarm action point is set by
deviation from the SV
(desired value) (except Process alarm).
When the input is out of the range, the output turns ON or OFF (in the case of High/Low limit
range alarm).
When the alarm action is set as De-energized, the output acts conversely.
• Setting accuracy
Thermocouple : Within
0.3% of each input span 1 digit, or
2
(4 ), whichever is greater
RTD
: Within
0.2% of each input span 1 digit
• Action
: ON/OFF action,
Hysteresis, 0.1 to 100.0
( )
• Output
: Open collector,
Control capacity, 24V DC
0.1A (maximum)
Loop break alarm output
When MV (manipulated variable) is maximum or minimum and when the PV does not change as
much as the preset span within the Loop break alarm assessment time, the alarm is activated.
Detects the breaking status on the loop such as heater burnout, sensor burnout or actuator trouble.
Output: Open collector
Control capacity, 24V DC
0.1A (maximum)