11.3 Control
Problem
Presumed cause and the action
Process variable
(temperature) does
not rise.
• Thermocouple or RTD may be burnt out.
Replace the sensor.
• Check whether Thermocouple or RTD lead wire is securely connected
to the instrument terminals.
• Ensure that the wiring of control output terminals is correct.
The control output (OUT)
remains in an ON
status.
• OUT low limit value is set to 100% or higher in Auxiliary function setting
mode 2.
Set it to a suitable value.
The control output (OUT)
remains in an OFF
status.
• OUT high limit value is set to 0% or less in Auxiliary function setting
mode 2.
Set it to a suitable value.
For all other malfunctions, please make inquiries at our agency or us.