48
(3)
(Scaling)
Converts the input of VOLT, TC and RTD to a corresponding value.
Setting the unit is possible. (See 7.1.3 on page 58)
Example: When setting the voltage of 0 to 40 mV and scale of 000.00 to 100.00 for Channel 1.
Press the “MENU” key for 3 seconds or longer to enter
setup mode. "
" is displayed, then press the
“ENT” key.
Use the
key to select the desired channel.
Press the “ENT” key.
Use the
key to select "
".
Press the “ENT” key.
Use the
key to select "
".
Press the “ENT” key. If
or
is selected
here, temperature input scaling is possible.
Use the
key to select a range (50 mV).
Press the “ENT” key.
Use the
key to select a numeral.
Use the
key to shift a digit. Press the “ENT” key.
Use the
key to select a numeral.
Use the
key to shift a digit. Press the “ENT” key.
FEED
ENT
(Span input value)
Display
Operation keys
Description
MENU
ESC
3 sec
ENT
ENT
ENT
ENT
ENT
FEED
ENT
(Zero input value)
[Note]
In the case of TC and RTD inputs, set the Zero input value equal to the Zero-side scale value. See
1 on the next page.
[Note]
In the case TC and RTD inputs, set the Span input value equal to the Span-side scale value.
See
2 on the next page.