13
When communication is not performed, the communication line for both host computer/PLC and controller
are in data Receiving status.
(*) Sending/Receiving switching time is determined by the selection of communication speed and
Sending/Receiving switching character.
(e.g.) Communication speed: 9600bps
Sending/Receiving switching character: 1 character
If 1 character is 10 bits, then Sending/Receiving switching time will be 0.001 seconds (1ms).
Communication timing
The IF-400 performs control within the
communication time above. Therefore, if data is transmitted with a
shorter interval than the Sending/Receiving switching time, normal communication cannot be performed.
Set the Sending/Receiving time from the host computer side so that the next piece of data can be sent
after the communication line is switched from Sending to Receiving status.
Turn the power ON
The PWR indicator lights when power supply to the unit is switched on.
Other indicators are unlit. (See Fig. 6-1)
(Fig. 6-1)
Basic setup operation
To proceed to the setup mode, press the key.
The unit will proceed to the “Communication speed selection” mode, and its characters will be
indicated on the display.
Make a selection using the and keys, and register the selected item with the key.
(See Fig. 6-2.)
(Fig. 6-2)
Unlit
Lit
Make a selection.
Proceeds to the Setup mode, and
registers the selected item.