5
4. Mounting
4.1 Site selection
Caution
Use within the following temperature and humidity ranges.
Temperature: 0 to 50 (32 to 122 ), Humidity: 35 to 85%RH (No icing, no condensation)
If the IF-400 is installed t within a control panel, the ambient temperature of the IF-400 must be kept to under 50 .
Otherwise the life of electronic parts (especially electrolytic capacitors) of the IF-400 will be shortened.
This unit is intended to be used under the following environmental conditions (IEC61010-1):
Overvoltage category
, Pollution degree 2
Ensure the mounting location corresponds to the following conditions
:
A minimum of dust, and an absence of corrosive gases
No flammable, explosive gases
No mechanical vibrations or shocks
No exposure to direct sunlight, an ambient temperature of 0 to 50 (32 to 122 ) that does not
change rapidly
An ambient non-condensing humidity of 35 to 85%RH
No large capacity electromagnetic switches or cables through which large current flows
No water, oil or chemicals or where the vapors of these substances can come into direct contact
with this unit
4.2 External dimensions
(Scale: mm)
(Fig.4.2-1)
4.3 Mounting to the DIN rail
Caution
Mount the DIN rail horizontally.
When the DIN rail is mounted vertically, be sure to use commercially available fastening plates at
the end of the IF-400. Mount the IF-400 to the DIN rail so that the IF-400 may be fixed.
However, if the DIN rail is mounted horizontally in a position susceptible to vibration or shock, the
fastening plates must be used as well.
•
Recommended fastening plate
Omron Corporation
End plate
PFP-M
IDEC Corporation
Fastening plate
BNL6
Matsushita Electric Works, Ltd. Fastening
plate
ATA4806
First
, hook
1
of the IF-400 on the upper side of the DIN rail. (Fig. 4.3-1)
Second
, making
1
part of the IF-400 as a support, fit the lower part
2
of the IF-400 to the DIN rail.
The IF-400
will be completely fixed to DIN rail with a “Click” sound. (Fig. 4.3-1)