38
Loop break alarm span
setting
0 to 150 ( ) or 0.0 to 150.0 ( )
For DC input: 0 to 1500
0
Non-volatile memory
data saving selection
0000H:
0001H: Data save
0002H:
0003H: Unable to save
0000H: Data save
Sensor correction
setting
-100.0 to 100.0 ( )
For DC input: -1000 to 1000
0.0
Scaling high limit
setting
Scaling low limit value to
Input range high limit value
1370
Scaling low limit setting
Input range low limit value to
Scaling high limit value
-200
Alarm 1 action selection
0000H: No alarm action
0001H: High limit alarm
0002H: Low limit alarm
0003H: High/Low limits alarm
0004H: High/Low limit range alarm
0005H: Process high alarm
0006H: Process low alarm
0007H: High limit alarm with standby
0008H: Low limit alarm with standby
0009H: High/Low limits alarm with
standby
0000H: No alarm
action
Alarm 2 action selection
The same as Alarm 1 action selection
0000H: No alarm
Alarm 3 action selection
The same as Alarm 1 action selection
0000H: No alarm
Alarm 4 action selection
The same as Alarm 1 action selection
0000H: No alarm
Alarm 1 hysteresis
setting
0.1 to 100.0 ( )
For DC input: 1 to 1000
1.0
Alarm 2 hysteresis
setting
0.1 to 100.0 ( )
For DC input: 1 to 1000
1.0
Alarm 3 hysteresis
setting
0.1 to 100.0 ( )
For DC input: 1 to 1000
1.0
Alarm 4 hysteresis
setting
0.1 to 100.0 ( )
For DC input: 1 to 1000
1.0
Alarm 1 action delayed
timer setting
0 to 9999s
0s
Alarm 2 action delayed
setting
0 to 9999s
0s
Alarm 3 action delayed
setting
0 to 9999s
0s
Alarm 4 action delayed
setting
0 to 9999s
0s
Control
Allowed/Prohibited
0000H: Control Prohibited
0001H: Control Allowed
0000H: Control
prohibited
Control
Allowed/Prohibited
when power-on
0000H: Control Prohibited when
power-on
0001H: Control Allowed when
power-on
0000H: Control
Prohibited when
power-on
Alarm 1 action
Energized/Deenergized
selection
0000H: Energized
0001H: Deenergized
0000H: Energized