55
Thermocouple and RTD input
Control range
• Range without a decimal point except for the RTD input:
Input range low limit value – 50 (100 ) to Input range high limit value + 50 (100 )
• Range with a decimal point including the RTD input without a decimal point:
–(Input span x 1%)
( ) to Input range high limit value + 50 (100 )
DC input
Control range: [Scaling low limit value – Scaling span x 1%] to [Scaling high limit
value + Scaling span x 10%]
DC input disconnection
(Table 12.5-3)
DC input type
Value when DC input is disconnected
4 to 20mA DC, 1 to 5V DC
(Scaling low limit value – Scaling span x 1%) or less
0 to 1V DC
(Scaling high limit value + Scaling span x 10%) or more
0 to 20mA DC
PV corresponding to 0mA DC
0 to 5V DC, 0 to 10V DC
PV corresponding to 0V DC
12.6 Sensor correction
The
PV is corrected when the temperatures in the controlled location differs from
those of the sensor location.
This is effective within the input rated range regardless of the sensor correction value.
12.7 PV filter
Reduces the effect of noise by including a first order
lag filter in the PV.
12.8 Power failure countermeasure
The setting data is backed up in the non-volatile IC memory.
12.9 Non-volatile memory data saving selection
If Non-volatile memory data [Unable to save] is selected during Non-volatile memory
data saving selection, all setting values except for the input type selection can be
changed temporarily. However, when the power to the unit is turned on again, those
values revert to the values set before the Non-volatile memory data [Unable to save]
was selected.
13. Specifications
13.1 Standard specifications
Rating
Rated scale
(Table 13.1-1)
Input Scale
range
Resolution
-200 to 1370
-320 to 2500
1 ( )
K
-199.9 to 500.0
-199.9 to 932.0
0.1 ( )
J
-200 to 1000
-320 to 1800
1 ( )
R
0 to 1760
0 to 3200
1 ( )
S
0 to 1760
0 to 3200
1 ( )
B
0 to 1820
0 to 3300
1 ( )
E
-200 to 800
-320 to 1500
1 ( )
T -199.9
to
400.0
-199.9 to 750.0
0.1 ( )
N
-200 to 1300
-320 to 2300
1 ( )
PL-
0 to 1390
0 to 2500
1 ( )
C(W/Re5-26)
0 to 2315
0 to 4200
1 ( )
-199.9 to 850.0
-199.9 to 999.9
0.1 ( )
Pt100
-200 to 850
-300 to 1500
1 ( )
-199.9 to 500.0
-199.9 to 900.0
0.1 ( )
M
JPt100
-200 to 500
-300 to 900
1 ( )