58
Alarm
Alarm 1 output
When Alarm 1 action is set as Energized, the alarm action point is set by
deviation from the SV (except Process value alarm).
When the input goes out of the range, the Event output turns ON or OFF (High/
Low limit range alarm).
When the alarm action is set as Deenergized, the output acts conversely.
Alarm type
One alarm can be selected from a choice of: High limit alarm, Low limit alarm,
High/Low limits alarm, High/Low limit range alarm, Process high alarm, Process low
alarm, High limit alarm with standby, Low limit alarm with standby, High/Low limits
alarm with standby and No alarm action (10 types). (Default value: No alarm action)
Alarm 1 output Energized or Deenergized can be selected as well.
Alarm 1 uses common output terminals with Loop break alarm, Heater burnout
alarm/Actuator short circuit alarm (W, W3 option).
When Heating/Cooling control output (DC option) is applied, Event output becomes
cooling output (OUT2). Therefore, Alarm 1, Loop break alarm and Heater burnout
alarm/Actuator short circuit alarm cannot be outputted.
Setting range
High limit alarm
–(Scaling span) to Scaling span
Low limit alarm
–(Scaling span) to Scaling span
High/Low limits alarm
0 to Scaling span
High/Low limit range alarm
0 to Scaling span
Process high alarm
Scaling low limit to Scaling high limit value
Process low alarm
Scaling low limit to Scaling high limit value
High limit alarm with standby
–(Scaling span) to Scaling span
Low limit alarm with standby
–(Scaling span) to Scaling span
H/L limits alarm with standby
0 to Scaling span
Setting to 0 or 0.0 disables the alarm action (excluding Process high alarm,
Process low alarm).
The negative minimum value is –199.9 or –1999, and the positive maximum
value is 999.9 or 9999.
For High limit alarm, High/Low limits alarm and Process high alarm, Alarm 1 is
activated in overscale, and the standby function of the alarms with standby
is released.
For Low limit alarm, High/Low limits alarm and Process low alarm, Alarm 1 is
activated in underscale, and the standby function of the alarms with standby is
released.
Setting value
: Initial value is zero (0).
Setting accuracy
: The same as the input accuracy
Action
: ON/OFF action
Alarm hysteresis setting range
: 0.1 to 100.0 ( ) (Default value: 1.0 )
DC input: 1 to 1000
Output
: Open collector
Control capacity, 0.1A 24V DC