61
Action point
: Setting value
Action
: ON/OFF action
Output
: Open collector, Control capacity 0.1A 24V DC
Heater burnout alarm 1 (W, W3 option)
When control output is ON, and if CT1 input value (detected
current) is lower than Heater burnout alarm 1 set value, this
alarm is activated
If CT1 input value (detected current) is higher than Heater
burnout alarm 1 set value, this alarm will not be activated.
Heater burnout alarm 2 (W3 option)
When control output is ON, and if CT2 input value (detected
current) is lower than Heater burnout alarm 2 set value, this
alarm is activated.
If CT2 input value (detected current) is higher than Heater
burnout alarm 2 set value, this alarm will not be activated.
Actuator short circuit alarm 1 (W, W3 option)
When control output is OFF, and if CT1 input value (detected
current) is higher than Heater burnout alarm 1 set value, this
alarm is activated.
If CT1 input value (detected current) is lower than Heater
burnout alarm 1 set value, this alarm will not be activated.
Actuator short circuit alarm 2 (W3 option)
When control output is OFF, and if CT2 input value (detected
current) is higher than Heater burnout alarm 2 set value, this
alarm is activated.
If CT2 input value (detected current) is lower than Heater
burnout alarm 2 set value, this alarm will not be activated.
• Heater burnout alarm 1 (2) • Actuator short circuit alarm 1 (2)
(Fig. 13.2-1)
(Fig. 13.2-2)
• CT connection for the W3 option
Pass two wires out of R, S, T through
the CT hole.
(Fig.
13.2-3)
Heating/Cooling control output (Option code: DC)
If this option is applied, Event output becomes cooling output (OUT2). Therefore,
Alarm 1, Loop break alarm and Heater burnout alarm/Actuator short circuit alarm
are not outputted.
OUT2 proportional band (P): 0.0 to 10.0 times OUT1 proportional band
(ON/OFF action when set to 0.0)
OUT2 integral time (I)
: The same as that of OUT1.
OUT2 derivative time (D)
: The same as that of OUT1.
OUT2 proportional cycle
: 1 to 120 seconds (Default value: 3 seconds)
Overlap band/Dead band : –100.0 to 100.0 ( ) (Default value: 0.0 )
DC input: –1000 to 1000 (The placement of the decimal
point follows the selection)
ON
OFF
ON
OFF
Setting
Setting
Large
Small
Small
Large
Load current
Load current
R
S
T