SR501 EN Operation Manual
- 23 -
The
“Auto” icon
disappear
Both of
“timing filling” and
“timing heating” are deactivate
Equivalent to summer
mode
5.3 Temperature controlled water filling function
Description:
When this function is activated, then water filling is controlled by temperature
which set by user. When sensor get the signal that water is not full filled and
water temperature is higher than the temperature for water filling, then controller
starts water filling automatically, when water temperature is 2
o
C below the set
temperature or water level is to 100% level, water filling is stopped.
When water is using (water level drops), to avoid water filling under this case,
water filling is delayed for 30minutes to start. (and default temperature
controlled time: 8:00-17:00).
Activate and deactivate the function, steps as below:
►Hold “Water Loading” button for 3 seconds to activate
temperature controlled water filling function
►Press “▲▼” button, to set temperature of water filling
( adjustable range
:
35
o
C-95
o
C, factory set: 60
o
C)
►Press “ESC” button to confirm the setting. The functions is activated.
► Hold “Water Loading” button for 3 seconds again to deactivate temperature
controlled water filling function.
Note:
when this function is activated, then the timing water filling is
deactivated.
6. Additional functions setting (for professionals)
Press
“SET” for 3 seconds to access the additional functions menu.
6.1 CTH Thermostat heating function
Description
: