SR501 EN Operation Manual
- 30 -
2) If the interval time ( CYCF) is set to 0 minute
,
then within the time-section,
DHW pump keeps running without any intervals. Close the tap, pump is
ceased automatically.
Default time sections:
-
The first time-section starts at 00:00 a.m., ends at 23:59 p.m.
-
The second time-section starts at 00:00 a.m., ends at 00:00 p.m.
-
The third time-section starts at 00:00 a.m., ends at 00:00 p.m.
Flow switcher fitting:
Material: Brass
House: plastics
Connection: G3/4
Reed: Max 300VDC/1A
Note
:
1
)
Pay attention to the water flow direction of flow switcher when you install it.
2
)
Flow switcher is connected to port T1 with either polarity.
3
)
Flow switcher is not included in the standard delivery list, if need please
purchase it separately.
4
)
Only one of two control modes can be selected to control DHW pump, it is
impossible to use them at the same time.
5
)
When water level of tank is lower than 20%, to avoid pump dry running
controller will deactivate the circulation pump automatically
Setup steps
(example with temperature controlled mode)
►Select menu TCYC to access the main menu and select menu “TCYC”.
►Press “SET” button again, “TCYC OFF” displays on
the screen.