SR501 EN Operation Manual
- 39 -
heater to heating tank to the required temperature to kill the bacteria. Therefore,
tank temperature is monitoring by controller at the monitoring period (PDIS)
(default is 7 days), if the temperature is not reached to the desired disinfection
temperature (TDIS) during this monitoring period PDIS, then controller will
trigger the electrical heater at the preset start time (SDIS), and controller will
heat tank and ensure the temperature during the heating period (DDIS) is
always higher than the desired disinfection temperature (TDIS). When thermal
disinfection function is working (DDIS time starts), DDIS countdown time starts
(default is 10 minutes), countdown time finished, thermal disinfection heating is
stopped, and then this function stops.
Setup steps
:
►Select TDIS thermal disinfection main menu
►Press “SET” button, “OTDI OFF” displays on the
screens
►Press “SET” button, “OFF” blinks
►Press“▲▼” button, to activate this function
►Press “SET” or “ESC” to confirm
►Press“▲”button, to set the temperature of disinfection, “TDIS 70
o
C
”displays
on the screen.
►Press “SET” button, “70
o
C
” blinks
►Press“▲▼”button, to set the temperature of thermal
disinfection, adjustable range is 60-90
o
C
,
factory set is
70
o
C.
►Press “SET” or “ESC” to confirm
Note:
Under standby status, hold
“ESC” button to access the inquiry function, there
you can check the on or off status of this function.