13
Technical data
13.1
Data sheet
Table 17: General data
≤ 1.1 m (for an object resolution of 70 mm), details:
Warning field range
≤ 4.0 m
1)
Fields
≤ 8
Field sets
≤ 4
Monitoring cases
≤ 4
Scanning angle
150° (15° … 165°)
Object resolution
50 mm, 70 mm, 150 mm, 200 mm
Maximum object speed
1.6 m/s
≤ 6°
Vertical aperture angle
≤ 4°
≤ 60 ms (for multiple sampling = 1), details:
≤ 46 ms
Switch-on delay of OSSDs
< 180 ms
≥
120 ms
Generally necessary protec‐
tive field supplement (TZ = tol‐
erance zone of the safe multi‐
beam scanner)
100 mm
Additional protective field
supplement Z
E
for back‐
ground-related measurement
error
220 mm, details:
supplement for background-related mea‐
Multiple sampling
1 ... 4
1)
At a minimum object size of 70 mm and a remission of 80%.
Table 18: Safety-related parameters
Type
Type 2 (IEC 61496-3)
Safety integrity level
SIL 1 (IEC 61508)
SIL claim limit
SILCL 1 (IEC 62061)
Category
Category 2 (ISO 13849-1)
Performance level
PL c (ISO 13849-1)
4 / h
Minimum internal test rate
400 / h
PFH
D
(mean probability of a
dangerous failure per hour)
1.3 x 10
-6
T
M
(mission time)
20 years (ISO 13849-1)
Safe status when a fault
occurs
At least one OSSD is in the OFF state.
Table 19: Interfaces
Automated restart of OSSDs
after
Immediately or between 2 s ... 60 s (configurable)
TECHNICAL DATA
13
8025936/2021-01-08 | SICK
O P E R A T I N G I N S T R U C T I O N S | scanGrid2 I/O
73
Subject to change without notice