Table 13: TPDO1, entry 7 (warning field status)
Bit
Name
Description
0
Status of the warning field in monitoring case
1:
0 = Interrupted
1 = Free
1
Status of the warning field in monitoring case
2:
0 = Interrupted
1 = Free
2
Status of the warning field in monitoring case
3:
0 = Interrupted
1 = Free
3
Status of the warning field in monitoring case
4:
0 = Interrupted
1 = Free
4
Status of the warning field in monitoring case
5:
0 = Interrupted
1 = Free
5
Status of the warning field in monitoring case
6:
0 = Interrupted
1 = Free
6
Status of the warning field in monitoring case
7:
0 = Interrupted
1 = Free
7
Status of the warning field in monitoring case
8:
0 = Interrupted
1 = Free
TPDO2 to TPDO9
The safe multibeam scanner sends the distance values of the eight sensor modules to
the detected objects via the objects TPDO2 to TPDO9.
The objects TPDO2 to TPDO9 use the same index 0x6204. Each of the objects consists
of four entries, each 16 bits in size.
This gives a total of 32 subindexes containing the distance values of the segments,
. Each entry contains the distance value of a segment of the safe
multibeam scanner.
If a segment of the safe multibeam scanner has not detected an object, a distance
value of 4,011 mm is output.
NOTE
When transmitting distance values using the objects TPDO2 to TPDO9, there must be
no node IDs > 63 within the network.
Table 14: TPDO2 contents
Entry
Index
Subindex
Description
1
0x6204
1
Distance value (mm) for segment 1
PROJECT PLANNING
4
8025990/2021-03-03 | SICK
O P E R A T I N G I N S T R U C T I O N S | scanGrid2 CANopen
35
Subject to change without notice