Figure 21: Device window (“Overview” page)
7.6
Configuring the safe multibeam scanner (Safety Designer)
Overview
The configuration of the safe multibeam scanner is initially performed on the computer
only and is saved in your Safety Designer project. This section describes the procedure
for configuring the device in Safety Designer and which configuration options you have.
To configure a safe multibeam scanner, you need to select the device in your project
and open it in the device window.
Approach
1.
In the main navigation menu of the device window, click on
Configuration
.
✓
The
Configuration
menu opens. The different pages within the configuration are
displayed in the
Navigation
area.
2.
In the
Navigation
area, click on
Identification
.
✓
The
Identification
page opens. On this page, you specify the device name, applica‐
tion name and other attributes (
).
3.
In the
Navigation
area, click on
Fields
.
✓
The
Fields
page opens. On this page, you create the field sets with fields and set
the object resolution and multiple sampling (
4.
In the
Navigation
area, click on
Monitoring cases
.
✓
The
Monitoring cases
page opens. On this page, you create the different monitoring
cases for the device (
see "Monitoring cases", page 75