Commissioning
Chapter
4
Operating Instructions
18
© SICK AG
•
Germany
•
All rights reserved
8014012/1EF3/2021-12-08
Subject to change without notice
4.3.3
Preset
A3M60 Basic
WARNING
Note
Fig. 5: Hardware manager
in the SIMATIC
The encoder is set to a pre-defined value by pressing the pushbutton. The value pre-
defined from the factory is zero (0).
The function is used for electronic adjustment during commissioning to allocate a specific
position value to a mechanical position of the shaft encoder (see also section 3.4.4 on
page 12).
After triggering the preset function, check whether there is a hazard from the machine
or system in which the encoder is integrated!
The preset function results in a change in the position value output by the encoder. This
change could cause an unexpected movement that may result in a hazard for persons or
damage to the system or other items.
4.4
Configuration
All software instructions refer to the STEP7 configuration tool for the SIMATIC.
4.4.1
Loading GSD file (once only)
►
Open the hardware manager for your PLC.
►
Install the GSD file STEG0CA7.gsd for the A3M60 Basic using the
Options
menu,
Install
GSD file...
command.
You will find the GSD file on the Internet at www.sick.com.
The A3M60 Basic appears in
Additional Field Devices
.