Startup and configuration
7.4.4
Save, display and print the current parameter set
When archiving a parameter set it is recommended to not only save the project file on the
PC but also print out the contents of the file.
1. In order to save the current parameter set, select the menu item S
AVE
P
ROJECT
AS
in the
menu bar under P
ROJECT
.
2. Enter a file name in the dialog window and confirm it via S
AVE
.
The SOPAS-ET configuration software saves the current settings in a configuration file
“*.spr“.
3. In order to print out the current parameter set, select the command P
RINT
/P
RINT
P
REVIEW
in the menu bar under P
ROJECT
.
The SOPAS-ET configuration software displays a preview of a table with a list of all the
parameter values.
4. Click on
in the tool bar at the top of the dialog window.
The dialog window P
RINT
for the printer configuration appears.
5. Edit setting accordingly and confirm with OK.
The current project settings are printed as a table on several pages.
TIP
To save the current parameter set as a PDF, select the P
RINT
/S
AVE
AS
PDF F
ILE
command in
the menu bar under P
ROJECT
.
7.5
Default setting
The values of the default setting are permanently saved in the bar code scanner (ROM) and
in the database of the SOPAS-ET configuration software in the device-specific jar file (see
chapter 7.4 First startup, page 70
). A PC is not required to start up the bar code scanner
with the default setting.
7.5.1
Resetting the default setting in the bar code scanner
Prerequisite
The SOPAS-ET configuration software is connected online to the bar code scanner.
Two default setting types can be called up via the SOPAS-ET configuration software:
•
Complete default setting (L
OAD
FACTORY
DEFAULT
)
SOPAS-ET resets all parameter values of the bar code scanner to default. Settings
which have been previously made for the communication parameters of the Ethernet
interfaces or serial data interfaces (e.g. Ethernet address) are overwritten. The connec-
tion(s) to the bar code scanner might be interrupted and has (have) to be reconfigured.
•
Application-specific default setting (L
OAD
APPLICATION
DEFAULT
)
SOPAS-ET resets the parameter values of the bar code scanner but does not change
the communication parameters. Settings which have been previously made for the
communication parameters of the Ethernet interfaces or serial data interfaces are kept
and the current connection(s) to the bar code scanner remain(s) established.