PROJECT PLANNING
4
19
8017621/ZPQ5/2017-08-15|SICK
Subject to change without notice
S U P P L E M E N T A R Y O P E R A T I N G I N S T R U C T I O N S | AOS502 STS
The test fields on the right and left must clearly and reliably impinge on the crane girders.
Take into account tolerances resulting from mechanical movements.
In order to avoid reflections on the surface of the external test target, the area of the test
target must not be covered with a glossy coating.
Ideally, the test target should be outside the longest monitoring field (approx. 0.5 m from
the edge of the monitoring field). A standard value for the distance from the laser scanner
is > 0.5 m. The width of the test field on the test target must be at least 100 mm.
Fig. 12: Alignment of the test target on the crane body