7.3
Adjust the device
For complete adjustment of the device, the electrical installation must be complete and
the device must have been commissioned.
1.
Loosen the bracket screws so that the device can be aligned.
2.
Align the device so that the angle between the scanning line and the bar code
stripes is almost 90°.
3.
To prevent interference reflections, arrange the device as close to being plane-par‐
allel to the object surface as possible.
4.
Manually place objects with bar codes one after the other into the reading range
of the device,
.
5.
Check the reading result with the SOPAS ET configuration software.
6.
When doing so, place objects at different positions (angles) in the reading field
and ensure that the limit values for the permitted reading angles are not
exceeded,
see "Angle alignment of the device", page 23
.
7.
Align the device so that the good read rate is between 70% and 100%.
8.
Tighten the screws on the device.