Example: Isolated connection of OSSD1 and OSSD2
Figure 27: Dual-channel and isolated connection of OSSD1 and OSSD2
Avoiding any potential difference between load and protective device
If you connect loads to the output signal switching devices (switching outputs) that
then also switch if controlled with negative voltage (e.g., electro-mechanical contactor
without reverse polarity protection diode), you must connect the 0 V connections of
these loads and those of the corresponding protective device separately and also
directly to the same 0 V terminal strip. In the event of a fault, this is the only way to
ensure that there can be no potential difference between the 0 V connections of the
loads and those of the corresponding protective device.
Figure 28: No potential difference between load and protective device
Further topics
•
"Integration in electrical control", page 22
•
6.2
System connection (M12, 5-pin)
2
1
4
3
5
Figure 29: System connection (male connector, M12, 5-pin)
6
ELECTRICAL INSTALLATION
42
O P E R A T I N G I N S T R U C T I O N S | deTec2 Core
8014276/1DCM/2022-10-27 | SICK
Subject to change without notice