Note
NOTE
The MQTT client ID may only consist of alphanumeric characters ([a-z][A-Z][0-9]).
“Ports” tab
Settings for connection ports S1 to S8 can be changed in the “Ports” tab. There is a
separate subpage for each port of the SIG350.
The setting for pin 4 and pin 2 can be made individually on each bottom side. For
example, the minimum cycle time or the port designation (deviceAlias) can be changed
here.
The Data Storage function can be configured for Restore or Restore according
to the desired use case. If data storage is to be used, Device ID and Vendor ID must be
set.
In addition, further information on the port status, such as communication status, but
also diagnostic data of the respective pins with regard to current and voltage and
temperature, is displayed.
If the Data Storage function has been activated, the complete contents of the data
storage container of a port can be transmitted from one SIG350 to a second SIG350.
For this purpose, the “Download data storage object” button for downloading from
one SIG350 and the “Upload data storage object” button for uploading to the second
SIG350 can be used. The exchange format is JSON.
“Devices” tab
On the Devices tab, the device-specific information of the connected IO-Link device is
displayed. There is a separate subpage for each port of the SIG350.
On each subpage, both the process data and the parameter data can be read out or
configured.
IO-Link data can be read from the connected device (Device to Master), but commands
can also be issued to the connected device (Master to Device). Process data from or to
the IO-Link device is transported cyclically via the fieldbus.
For parameter data, it is necessary that these are explicitly requested by the master.
They are transmitted acyclically.
8
OPERATION
60
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350
8027836./2022-06-10 | SICK
Subject to change without notice