6.4
Derating
Observe the derating when using the SIG350. The ambient temperature and the current
have an influence on the heating of the module.
The product provides temperature and current readings that you can display via the
web interface or read out via Dual Talk interfaces.
The following figure shows the maximum permissible current (I) that may be drawn by
the device, depending on the ambient temperature (T):
I [A]
16
14
12
10
8
6
4
2
0
-30 -20 -10
0
10 20 30 40 50 60 70
T [°C]
Figure 8: Derating sensor current US/actuator current UA
I [A]
16
14
12
10
8
6
4
2
0
-30 -20 -10
0
10 20 30 40 50 60 70
T [°C]
Figure 9: Derating total current IO-Link ports (total current S1 – S8)
I [A]
2.5
2
1.5
1
0.5
0
-30 -20 -10
0
10 20 30 40 50 60 70
T [°C]
Figure 10: Derating current per sensor supply and output (per pin 1, 2, and 4 at IO-Link port S1 –
S8)
ELECTRICAL INSTALLATION
6
8027836./2022-06-10 | SICK
O P E R A T I N G I N S T R U C T I O N S | Sensor Integration Gateway - SIG350
23
Subject to change without notice