12.4.3
Calibration times for automatic calibration
Function
Automatic calibration operations can be programmed at specific times. Three start times
can be set for each weekday. The start times can be activated and deactivated individually
(
Y
/
N
).
These settings are only effective if the
C a l . m o d e
is set to
a u t o
).
Procedure
1
Open the menu: Main menu
Maintenance
System Parameters
User level
Calibration control
Calibration time
2
Move the highlighting to the respective field with the
keys.
3
In the entry fields:
Enter the required value
(hour:
0 0
…
2 3
/ minute:
0 0
…
5 9
).
In the selection boxes: Press
until the required setting is displayed (
Y
: Start time is
applied /
N
: is ignored).
To finish:
4
Press
or
, until
E n d
is highlighted.
5
Press .
Recommended calibration interval: 1 week
●
If the “Calibration block” control input (
) is activated, no
calibration operations are started.
●
If a start time is blocked as a result, the respective calibration is
automatically run as soon as the “Calibration block” control input is
deactivated.
C a l i b r a t i o n t i m e
S u n d a y :
N 0 0 : 0 0 Y 1 2 : 0 0 N 0 0 : 0 0
M o n d a y :
Y 0 7 : 3 0 N 1 0 : 1 5 Y 1 9 : 4 5
T u e s d a y :
N 0 0 : 0 0 N 0 0 : 0 0 N 0 0 : 0 0
W e d n e s d a y :
N 0 7 : 3 0 Y 1 0 : 1 5 Y 1 9 : 4 5
T h u r s d a y :
N 0 0 : 0 0 N 0 0 : 0 0 N 0 0 : 0 0
F r i d a y :
N 0 7 : 3 0 Y 1 0 : 1 5 Y 1 9 : 4 5
S a t u r d a y :
N 0 0 : 0 0 N 1 2 : 0 0 Y 2 3 : 3 0
C h a n g e o r
Menu title
Weekday
Selection box for activation/entry fields for the hour:minute
It can take several seconds to save the values
(display message:
P l e a s e w a i t
).
E n d
Summary of Contents for EuroFID
Page 10: ...Contents 10 EuroFID Operating Instructions 8011094 V2 3 SICK AG ...
Page 18: ...18 EuroFID Operating Instructions 8011094 V2 3 SICK AG Important Information ...
Page 80: ...80 EuroFID Operating Instructions 8011094 V2 3 SICK AG Start up ...
Page 88: ...88 EuroFID Operating Instructions 8011094 V2 3 SICK AG Operation General ...
Page 100: ...100 EuroFID Operating Instructions 8011094 V2 3 SICK AG Main Menu Functions ...
Page 144: ...144 EuroFID Operating Instructions 8011094 V2 3 SICK AG Maintenance Sub menu Functions ...
Page 154: ...154 EuroFID Operating Instructions 8011094 V2 3 SICK AG Calibration ...
Page 158: ...158 EuroFID Operating Instructions 8011094 V2 3 SICK AG Shutdown ...
Page 182: ...182 EuroFID Operating Instructions 8011094 V2 3 SICK AG Clearing Malfunctions ...