Bidirectional use
Two straight pipes are to be installed in the inlet and outlet sections if the meter is to be
used bidirectionally. The temperature measuring point is to be located downstream of the
FLOWSIC600, seen in the direction of predominant use. The temperature measuring point
must not be installed more than 8 DN from the meter.
Figure 46
FLOWSIC600 installation in the pipeline for bidirectional use
10 DN
FLOWSIC600
min. 5 DN min. 5 DN
min. 2 DN min. 3 DN min. 3 DN min. 2 DN
1 .. 5 DN 1 ..5 DN
min. 2 DN min. 7 DN min. 7 DN min. 2 DN
Alternative temperature measuring points
Flow conditioner
Flow conditioner
Alternative temperature measuring points
5 ..8 DN
5 .. 8 DN
DN
Configuration 1
Configuration 2a
Configuration 2b
Applicable for meters
marked with an asterisk
(*) in
5 DN
5 DN
10 DN
10 DN