Approach
1.
Select the column with the right time and set the respective scale switch to posi‐
tion 1.
2.
Select the line with the right time and set the respective time switch to position 1.
Example
To select a release delay of 1.5 s, scale switch 2 and time switch 3 must be set to posi‐
tion 1.
Sc
ale
T
ime
in s
5
10
15
30
0
1
CS
EMSS
OSSD
0.8
1
1.5
2
0.1
0.2
0.3
0.5
Figure 12: Release delay example
Complementary information
You can only activate one time, i.e. set a combination of time and scale switches.
Further topics
•
"Activating configuration", page 24
7.3
Configuring sensor type
Prerequisites
The safety relay is disconnected from the voltage supply.
Approach
You can configure the sensor type connected to the safety relay here.
b
OSSD sensor type: If there are sensors with OSSD outputs connected to the safety
relay, set the OSSD switch to position 1.
b
EMSS sensor type: If sensors and safety devices with volt-free contact outputs are
connected to the safety relay, set the EMSS switch to position 1.
Complementary information
You can only configure one sensor type.
Further topics
•
"Compatible sensor types", page 10
•
"Activating configuration", page 24
CONFIGURATION
7
8024303/2019-12-18 | SICK
O P E R A T I N G I N S T R U C T I O N S | ReLy TIME1
23