Electrical installation
Connecting the supply voltage
When wiring the interrogator using connection module CDB620 or CDM420, the interroga-
tor's data and function interfaces are contacted to the connection module together with the
power supply.
1. Ensure that the connection module's supply voltage has been switched off.
2. Standard version: connect the bar code scanner's 15-pole cable plug to the connection
module's 15-pole socket and screw it tight.
- or -
Ethernet version: connect the interrogator's 12-pole plug via a corresponding cable
(e.g., no. 2042916) to the connection module's 15-pole socket and screw it tight.
6.4.2
Wiring serial data interfaces
The maximum data transfer rate of the serial data interface depends on the cable length
and the interface type.
Tab. 6-6:
Recommended maximum cable lengths, depending on the selected data transfer rate
Fig. 6-2:
Wiring the serial host data interfaces (RS-232 and RS-422 respectively) on the 15-pole
D-Sub-HD plug
Interface type
Transfer rate
Distance to the host
RS 232
up to 19,200 Bd
Max. 10 m (32.8 ft)
38,400 ... 57,600 Bd
Max. 3 m (9.84 ft)
115,200 Bd
Max. 2 m (6.56 ft)
RS-422/485
1)
max. 38,400 Bd
max. 1,200 m (3,937 ft)
max. 115,200 Bd
max. 500 m (1,640 ft)
1)
in corresponding line termination according to the specification
CLV
Host
Host
CLV
RS-232
RS-422