6)
In the case of a fault (0 V cable open circuit), no more than the specified leakage current flows in the
OSSD cable. The downstream control element must detect this state as LOW. An FSPLC (fail-safe pro‐
grammable logic controller) must detect this state.
7)
If the switching sequence is low, the maximum permissible load inductance is higher.
8)
Make sure to limit the individual conductor resistances to the downstream controller to this value to
ensure that a cross-circuit between the outputs is safely detected. (Also note EN 60204-1.)
9)
When active, the outputs are tested cyclically (brief LOW). When selecting the downstream controllers,
make sure that the test pulses do not result in deactivation.
12.2
Characteristic curves
Scanning range for warning fields
1
2
5
10
20
50
100
200
500
0,1
0,2
0,5
1
2
5
10
20
50
1
2
3
4
5
6
R [%]
D [m]
Figure 60: Diagram scanning range with Long Range sensor head
R
Necessary minimum radiance factor in %
D
Scanning range in m
1
Black shoe leather
2
Matt black paint
3
Gray cardboard
4
Writing paper
5
White plaster
6
Reflectors > 2,000%, reflective tapes > 300%
12
TECHNICAL DATA
112
O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store
8012029/ZA20/2019-11-14 | SICK
Subject to change without notice