Complementary information
NOTE
You can configure the warning field up to 49 m for all resolutions. The detection capa‐
bility within the warning field depends on the radiance factor of the objects to be
detected.
Further topics
•
"Characteristic curves", page 112
7.6.2
Basic response time
The basic response time depends on the angular resolution selected and is:
•
60 ms basic response time at 0.5° angular resolution
•
120 ms basic response time at 0.25° angular resolution
NOTE
You may need to add supplements to the basic response time due to multiple sampling
and data transmission over EFI.
Further topics
•
7.6.3
Angular resolution and maximum protective field range
The angular resolution affects the maximum protective field range and the basic
response time.
Two angular resolutions can be configured:
•
At 0.5° angular resolution the basic response time is 60 ms.
•
At 0.25° angular resolution the basic response time is 120 ms.
NOTE
•
The maximum protective field range of the safety laser scanner must be sufficient
to cover the calculated protective field size including the necessary supplements.
Further topics
•
•
"Basic response time", page 70
•
"Protective field size", page 39
7.6.4
Field mode
Dual
If you select the
Dual
option, you can configure field sets that comprise two fields: one
protective field and one warning field.
If you select the
Dual
option, simultaneous monitoring is available. This enables two pro‐
tective fields and two warning fields to be evaluated.
Dual protective fields
If you select the
Dual protective fields
option, you can configure field sets that comprise
two protective fields. Here both fields are evaluated as safe fields.
If you select the
Dual protective fields
option, simultaneous monitoring is available. This
enables four protective fields to be evaluated.
7
CONFIGURATION
70
O P E R A T I N G I N S T R U C T I O N S | S3000 Cold Store
8012029/ZA20/2019-11-14 | SICK
Subject to change without notice