Complementary information
NOTE
You can configure the warning field up to 49 m for all resolutions. The detection capa‐
bility within the warning field depends on the radiance factor of the objects to be
detected.
Further topics
•
"Characteristic curves", page 145
7.6.2
Basic response time
The basic response time depends on the angular resolution selected and is:
•
60 ms basic response time at 0.5° angular resolution
•
120 ms basic response time at 0.25° angular resolution
NOTE
You may need to add supplements to the basic response time due to multiple sampling
and data transmission over EFI.
Further topics
•
7.6.3
Angular resolution and maximum protective field range
The angular resolution affects the maximum protective field range and the basic
response time.
Two angular resolutions can be configured:
•
At 0.5° angular resolution the basic response time is 60 ms.
•
At 0.25° angular resolution the basic response time is 120 ms.
NOTE
•
The maximum protective field range of the safety laser scanner must be sufficient
to cover the calculated protective field size including the necessary supplements.
•
On the S3000 Expert and S3000 Remote, the number of field sets that can be
configured depends on the angular resolution selected.
Further topics
•
•
"Basic response time", page 89
•
"Protective field size", page 42
•
7.6.4
Field mode
Dual
If you select the
Dual
option, you can configure field sets that comprise two fields: one
protective field and one warning field.
If you select the
Dual
option, simultaneous monitoring is available. This enables two pro‐
tective fields and two warning fields to be evaluated.
CONFIGURATION
7
8009942/ZA18/2019-11-14 | SICK
O P E R A T I N G I N S T R U C T I O N S | S3000
89