The identifier uses the following syntax:
°
Words comprise [a-z0-9-].
°
Words do not start with [-].
°
Words do not end with [-].
°
The first word must not have the form port-xyz or port-xyz-abcde (a, b, c, d, e
and x, y, z = 0 … 9).
°
Identifiers must not have the form n.n.n.n (n = 0 … 999).
The following also applies when naming an MRP domain:
•
The total length of the identifier must be 3, 7, 11, 15, 19, … characters.
7.5
Configuring PROFINET IO
You can find an application and programming example for configuring the S3000
PROFINET IO/IO-OF and an FPLC under the respective part number in the download
area on www.mysick.com.
7.5.1
Reading the generic station description (GSDML)
Overview
Before you can configure PROFINET IO for the first time for the S3000 PROFINET IO/IO-
OF, you must add the generic station description (GSDML
2)
) for the S3000
PROFINET IO/IO-OF to the hardware catalog in the network engineering tool, e.g., the
SIMATIC Manager (Siemens) for PROFINET IO.
Approach
1.
On the web page
, enter the part number in the search field and
download the GSDML file.
2.
To load the generic station description file, follow the instructions in the online
help or in the user manual of the network engineering tool.
✓
The S3000 PROFINET IO/IOOF now appears in the hardware catalog in the net‐
work engineering tool under
>
Additional Field Devices
>
Sensors
>
SICK
.
2)
GSDML = Generic station description based on XML.
7
CONFIGURATION
68
O P E R A T I N G I N S T R U C T I O N S | S3000 PROFINET IO, S3000 PROFINET IO-OF
8013291/ZA19/2019-11-14 | SICK