Bit
Description
Bit 5
Device communication (DevCom)
0 = No device available
1 = Device detected and in PREOPERATE or OPERATE state
Bit 4
Port activation (PortActive)
0 = Port deactivated via port function
1 = Port activated
Bit 3
Substitute device detection (SubstDev)
0 = No substitute device detected (identical serial number)
1 = Substitute device detected (different serial number)
Bit 2
New parameter (NewPar)
0 = No change of the device parameter detected
1 = Change of device parameter detected: Master has per‐
formed a data memory upload and a new IOLD backup object
(0xB904) is available
Logic editor process data (slot 1, subslot 2)
The following process data submodules are available for the logic editor (slot 1, sub‐
slots 2):
Submodule
name
Direc‐
tion
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Logic editor
2I / 0O
On
0
2 byte logic editor data input
1
Logic editor
0I / 2O
Off
0
2 byte logic editor data output
1
Logic editor
2I / 2O
On
0
2 byte logic editor data input
1
Off
0
2 byte logic editor data output
1
SIG200 CONFIGURATION
7
8017853.1D0S/2021-11-04 | SICK
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
25