Properties
Value
PROFINET access
Commissioning protocol for all IO-Link device submodules (except
"Digital input", "Digital output"; slot 2, subslot 2 to 5)
Byte 8 to 11: Expected device ID
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, byte 8 to 11: Expected
device ID
Coding
Any
Expected device ID of the IO-Link device connected to
the IO-Link port (unsigned integer 32)
Example:
Device ID
7.1.2.2.1.6
Port cycle time
Port cycle time
can be used to define the minimum cycle time used by the IO-Link master
on a specific IO-Link port.
Properties
Value
PROFINET access
Commissioning protocol for all IO-Link device submodules (except
"Digital input", "Digital output"; slot 2, subslot 2 to 5)
Byte 12: Port cycle time
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, byte 12: Port cycle time
Coding
0
As soon as possible
16
1.6 ms
32
3.2 ms
48
4.8 ms
68
8.0 ms
100
20.8 ms
133
40 ms
158
80 ms
183
120 ms
7.1.2.2.1.7
Input data length
With
Input data length
, the current input data length can be read out (from a provided
IODD or determined during startup of the IO-Link device).
NOTE
In PROFINET, the input data length also contains the PQI byte (
Port Qualifier Information
).
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, byte 13: Input data
length
Coding
0…33
Number of bytes in the incoming IO-Link device process
data (via PROFINET interface, including PQI byte)
7.1.2.2.1.8
Output data length
With
Output data length
, the current output data length can be read out (from a provided
IODD or determined during startup of the IO-Link device).