7.1.2.2.1.12
Master cycle time
With
Master cycle time
, the actual cycle time at this port can be read out.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 9: Master cycle
time
Coding
Bit 7…6 Time Base
00
0.1 ms calculation: Multiplier x time base
01
0.4 ms calculation: Multiplier x time base +6.4 ms
10
1.6 ms calculation: Multiplier x time base +32 ms
Bit 5…0 Multiplier
7.1.2.2.1.13
Actual manufacturer ID
With
Real Vendor ID
, the actual vendor ID of a connected IO-Link device can be read out
at this port.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 10 to 11: Actual
manufacturer ID
Coding
Manufacturer ID of the IO-Link device connected to the IO-Link
port (unsigned integer 16)
7.1.2.2.1.14
Actual device ID
With
Real Device ID
, the actual device ID of a connected IO-Link device at this port can be
read out.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 12 to 15: Actual
device ID
Coding
Device ID of the IO-Link device connected to the IO-Link port
(unsigned integer 32)
7.1.2.2.1.15
Event entries
Event entries
can be used to read out the number of supported event entries of a
connected IO-Link device at this port as well as the currently reported events.
NOTE
The byte count for this function is dynamic and depends on the number of available
event entries (1 byte for the number of entries and 3 bytes for each entry).
NOTE
The coding of the individual entries is based on the IO-Link event coding. A value of
0x000000 in the first event entry indicates that there are no events.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 16 to N: Event
entries
SIG200 CONFIGURATION
7
8017853.1D0S/2021-11-04 | SICK
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
39