Properties
Value
Coding
0
Automatic IO-Link parameterization: No explicit port
parameterization is used at this IO-Link port. Basic
assignments such as inspection level, port cycle time,
manufacturer ID, and device ID are not required.
1
IO-Link port parameterization active: Single-stage com‐
missioning is used at this IO-Link port. The explicit port
parameterization for inspection level, port cycle time,
manufacturer ID and device ID is done in the PLC via the
PROFINET engineering tool.
2
Parameterization with IO-Link tool: Two-stage commis‐
sioning is used at this IO-Link port. There is no explicit
port parameterization in the PLC via the PROFINET engi‐
neering tool. Port parameterization and device parame‐
terization can be performed using tools that support the
standardized PDCT interface (
Port and Device Configuration
Tool
).
NOTE
Port configuration mode
(port parameterization mode) must be set to
active
for the other
configuration parameters such as
Validation and data storage
to be applied.
7.1.2.2.1.2
Global diagnosis
Global diagnostics
can be used to define whether diagnostic messages are transmitted
from the SIG200 to the PLC.
This setting can only be called up via the PLC interface.
Properties
Value
PROFINET access
Commissioning protocol SIG200-IO-Link master (slot 1, subslot 1)
Byte 2, bit 1: GDIAG (global diagnostics)
Coding
0
Deactivate: All diagnostic messages from the SIG200 to
the PLC are deactivated (default setting).
1
Activate: Diagnostic messages from the SIG200 to the
PLC are activated.
7.1.2.2.1.3
Validation and data storage (inspection stages)
The settings for validation and data storage (inspection levels) can be used to define
the levels of compatibility testing of a connected IO-Link device. For more information
on usage as well as use applications, please see
Properties
Value
PROFINET access
Commissioning protocol for all IO-Link device submodules (except
"Digital input", "Digital output"; slot 2, subslot 2 to 5)
Byte 5: Validation and backup
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB100/0xB101/0xB102/0xB103, byte 5: Validation and
backup
SIG200 CONFIGURATION
7
8017853.1D0S/2021-11-04 | SICK
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200
35