11.2
7-segment Display
The 7-segment display at the device front panel shows status and error messages.
This display provides helpful information when errors occur.
Error codes consisting of up to 3 digits are read out. The last position of a multi-digit
code is characterized by a point. The numbers 0, 1 and 2 do not represent an error but
indicate an operating mode.
Examples:
1.
Permanent display 0
▶
Controller is switched off.
▶
No error.
2.
Permanent display 1
▶
Controller is switched on.
▶
No error.
3.
Permanent display 1.
▶
Controller is switched on.
▶
No error.
▶
Dot calls additional attention to PI limit.
4.
→
→
Sequential display
▶
Controller is switched off due to error E42.
▶
The error is not present anymore.
5.
→
→
Sequential display
▶
Controller is switched off due to error E42.
▶
The error is still present (indicated by the dot behind 'E').
7.
→
→
Sequential display
▶
Controller is in boot loader mode: Display appears short-time when
the device is booted and when the system software is loaded.
11.2.1
List of the Operating States
Code
Description
0
Ready to switch on
1
Controller active
1.
Controller active, controller is limited / PI limit
2
Mains 'Ready for operation' not present yet
L
Boot loader active (during boot / software load)
11.2.2
List of the Error Messages
Code
Error message
Error reaction
Possible reason
E06
(0x106)
Digital Input 'External Hardware'
The motor is disabled immediately.
▶
The digital input has been
programmed but not connected
to 24 V.
▶
The external hardware signals
an error.
E07
(0x107)
Error in internal hardware
(Monitoring functions of the digital
outputs.) The motor is disabled
immediately.
▶
Short circuit at the output
connector of the digital outputs.
▶
Defect output IC.
E10
(0x10A)
drive-setup-tool heartbeat
The motor is stopped immediately
and disabled.
▶
The communication line is
defect or disturbed.
▶
The control source failed.
Status Display and Error Messages
W
62
FC2 - Frequency converter 02192100xy
11
Summary of Contents for FC2
Page 4: ...Chapter Overview W 4 FC2 Frequency converter 02192100xy ...
Page 8: ...Content W 8 FC2 Frequency converter 02192100xy ...
Page 12: ...General Information W 12 FC2 Frequency converter 02192100xy 2 ...
Page 22: ...Unit Assembly Complying EMC W 22 FC2 Frequency converter 02192100xy 4 ...
Page 30: ...Technical Data W 30 FC2 Frequency converter 02192100xy 7 ...
Page 48: ...Connectors W 48 FC2 Frequency converter 02192100xy 8 ...
Page 70: ...Safety Circuit Restart Lock STO W 70 FC2 Frequency converter 02192100xy 12 ...