IV319 Rev.00
Data 2010-06-22
Pag. 13 di 118
3.2 Product Specification and Performance
1) General Specification
Model
6K 1/1
10K 1/1 (S)
10K 3/1 (S)
15K 3/1
20K 3/1
Power Rating
6KVA
4,2KW
10KVA
7KW
10KVA
7KW
15KVA
10,5KW
20KVA
14KW
Frequency (Hz)
50/60
50/60
50/60
50/60
50/60
Input
Voltage
(176-276)VAC (176-276)VAC (304-478)VAC (304-478)VAC (304-478)VAC
Current
32A max.
50A max
50A max
75A max
100A max
Battery
Voltage
240VDC
240VDC
240VDC
240VDC
240VDC
Current
24A max
40A max
40A max
60A max
80A max
Output
Voltage
208/220/230/240VAC
Current
26/27/26/25A 43/45/43/42A
43/45/43/42A
65/68/65/63A 87/91/87/83A
Dimension
(WxDxH) mm
260x570x717 260x570x717
260x570x717
260x570x717 260x570x717
Weight (kg)
90
93 (38)
94 (39)
55
55
Note: on 10K (S) are the version without internal battery
2) Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
1/1 6K / 10K
Single-phase 46-54Hz/56-64Hz
>0.98 (Full load)
3/1 10K / 15K / 20K
Three-phase
+ N
46-54Hz/56-64Hz
>0.95 (Full load)
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Current
crest ratio
1%
0.7 lag
Synchronized
46-54Hz/ 56-64Hz in
Line mode (AC
mode)
0.1% of normal
frequency in Battery
mode
THD<2%
Full load
(Linear
Load)
105%-130% load transfers to
Bypass mode after 10 minutes
>130% load transfers to Bypass
mode after 1 second and
shutdown the output after 1
minute
3:1
maximum
Summary of Contents for Green Point 6 20KVA
Page 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Page 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Page 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Page 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...