7. Battery Maintenance
Ⴠ
This series UPS only requires minimal maintenance. The battery
used for standard models are value regulated sealed lead-acid
maintenance free battery. These models require minimal repairs.
The only requirement is to charge the UPS regularly in order to
maximize the expected life of the battery. When being connected
to the utility power, whether the UPS is turned on or not, the UPS
keeps charging the batteries and also offers the protective
function of overcharging and over-discharging.
Ⴠ
The UPS should be charged once every 4 to 6 months if it has not
been used for a long time.
Ⴠ
In the regions of hot climates, the battery should be charged and
discharged every 2 months. The standard charging time should
be at least 12 hours.
Ⴠ
Under normal conditions ( temperature between 15°C and 25°C),
the battery life lasts 3 to 5 years. In case if the battery is found
not in good condition, earlier replacement should be made.
Battery replacement should be performed by qualified
personnel.
Ⴠ
Replace batteries with the same number and same type of
batteries.
Ⴠ
Do not replace the battery individually. All the batteries should be
replaced at the same time following the instructions of the
battery supplier.
Ⴠ
Normally, the batteries should be charged and discharged once
every 4 to 6 months. Charging should begin after the UPS shuts
down automatically in the course of discharging, the standard
charging time for the standard UPS should be at least 12 hours.
Summary of Contents for Green Point 6 20KVA
Page 28: ...IV319 Rev 00 Data 2010 06 22 Pag 28 di 118 Wiring diagram of 6K 10K 1 1 parallel system...
Page 29: ...IV319 Rev 00 Data 2010 06 22 Pag 29 di 118 Wiring diagram of 10K 3 1 parallel system...
Page 57: ...IV319 Rev 00 Data 2010 06 22 Pag 57 di 118 DB 9 Interface of AS400 communication protocol...
Page 61: ...IV319 Rev 00 Data 2010 06 22 Pag 61 di 118 Back View of 15K 20K 3 1...