IV306E Rev. 004 Siel S.p.A.
Page 28 of 37 + 12 Tables, 14 F FR
Issued date: 2014-03-24
To highlight the electrical voltage and current measurements of the highlighted event, use keys < V >,
<Hz-A> and V-A DC>.
See the example below.
MANUAL BATTERY TEST
To perform the battery test immediately, select the corresponding menu item.
Press the <SHIFT> + < > keys together: the message 'BATTERY TEST IN PROGRESS' will appear
on the display.
If after about 20 seconds the cyclical view of the UPS operating status is restored, the test has been
successfully performed.
If there is a problem with the battery, "BATTERY FAILURE" appears on the display and an acoustic
warning is heard.
The result of the test is stored until another battery test is carried out (manually or automatically).
BATTERY DISCHARGE TEST CONFIGURATION AT DUE TIME
To configure the battery discharge test it is necessary to select the corresponding item in the menu.
After this operation, the display will show parameters called <activate>, <day/time> and <No. of
weeks>. The first one, <activate>, can assume the value <YES>/<NO> and can be used to activate/de-
activate the battery discharge test.
The second parameter, <day/time>, makes it possible to enter the day of the week expressed with
<MON> ... <SUN> and the time when the discharge test is scheduled for. The third parameter, <n.
weeks>, indicates the number of weeks between one test and another; for instance, by setting 1 for this
item, the discharge test is performed every week. There are two more considerations:
a) If zero is set as a number of weeks, the discharge test will only occur during the first week.