ONNECTIONS OF THE MODEL WITH SEPARATE BYPASS
(O
PTIONAL
)
The very first connection to be carried out is that of the protection conductor (earth cable), which must
be connected to the terminal marked PE. The UPS must not operate without being connected to an
earthing system
THE INPUT AND THE BYPASS NEUTRALS MUST ALWAYS BE CONNECTED.
THE INPUT AND BYPASS LINES MUST REFER TO THE SAME NEUTRAL POTENTIAL.
DO NOT CONNECT THE OUTPUT NEUTRAL TO THE INPUT OR BYPASS NEUTRAL.
Connect the input and output cables to the terminal board as shown in the figure below:
Note 1
: The protection conductor (earth cable) connection must be carried out through eyelet terminal stud M6
Note 2:
Connections to the BATTERY module are required only when the optional Battery Box is present
C
ABLE ROUTING
It is recommended to wire the power cables routing them from the back, under the UPS, to the front of the machine, ensuring
they come up in the terminal area as shown:
The lower part of the structure also has slots that can be used to secure the cables using suitably sized clamps.
Summary of Contents for Safepower-Evo-HF 30
Page 2: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 2 di 258 FR...
Page 35: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 35 di 258 FR MENU DISPLAY...
Page 86: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 86 di 258 FR MENU DISPLAY...
Page 137: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 137 di 258 FR DISPLAY MEN...
Page 188: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 188 di 258 FR MENU AFFICHEUR...
Page 239: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 239 di 258 FR MEN PANTALLA...
Page 258: ...IV331 Rev 000 SIEL S p A Data di emissione 2011 08 22 Pag 258 di 258 FR...