IV405E Rev.000 SIEL S.p.A.
Data di emissione: 2018-06-22
Pag. 35 di 50 + FR
4.4.9 Periodical battery self-test Setting
Periodical battery self-test setting (note: the part in dashed box flashes)
In
the buzzer setting press “
ON
” or
in
parallel ID setting press “
OFF
”, it goes to the battery
self-test setting. In the meantime the setting state flashes as above picture shows (Note: ON 1- the
battery self-test function is enabled, UPS will do self-test 10 seconds every 30 days; ON 2- the
battery self-test function is enabled, UPS will do self-test 10 minutes every 30 days; ON 3- the battery
self-test function is enabled, UPS will do self-test till battery voltage reaches EOD point every 30 days;
OFF-battery self-test function is disabled.).
Press “
P
” to set
periodically self-test setting. The
options are OFF, ON 1, ON 2 and ON 3.
ཱ
Press
“
ON
” to exit Periodically Self
-test setting and save
the setting value, and goes to battery temperature compensation sensor switch setting.
ི
Press
“
OFF
” to exit Periodically Self
-test setting and goes to buzzer setting.
4.4.10 Battery temperature compensation sensor switch setting
Battery temperature compensation sensor switch setting
(Note: the information in the red box will be flashing)
Press
“
ON
”
under the periodical battery self-test setting or press
“
OFF
”
under device address
setting, goes to the battery temperature compensation switch setting. The setting state flashes as
above picture shows (Note: OFF means turn off the sensor switch, ON means turn on the sensor
switch, send query command to sensor with address 11,12 every second.
Ԙ
Press
“
P
”
is to set the
battery sensor, with options OFF & ON.
ԙ
Press
“
ON
”
to exit the battery sensor setting and save
the battery sensor setting value and transfer to device address setting.
Ԛ
Press
“
OFF
”
to exit the
battery sensor setting and transfer to battery periodical battery self-test setting.