IV405E Rev.000 SIEL S.p.A.
Data di emissione: 2018-06-22
Pag. 40 di 50 + FR
24
CAN comm. Fault
Twice per second
Fault LED lit
25
Parallel load sharing fault
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
27
Mains Site Wiring Fault
Once per second
Fault LED blinking
28
Bypass Site Wiring Fault
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Rectifier over current
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV
or
BPS
LED
blinking
33
No battery
Once per second
Battery LED blinking
34
Battery under voltage
Once per second
Battery LED blinking
35
Battery low pre-warning
Once per second
Battery LED blinking
36
Internal Communication Error
Once per 2 seconds
Fault LED blinking
37
DC component over limit.
Once per 2 seconds
INV LED blinking
38
Parallel Overload
Once per 2 seconds INV LED blinking
39
Mains volt. Abnormal
Once per 2 seconds Battery LED lit
40
Mains freq. abnormal
Once per 2 seconds Battery LED lit
41
Bypass Not Available
BPS LED blinking
42
Bypass unable to trace
BPS LED blinking
43
Inverter on invalid
44
Reserve
45
inverter not on
4.4 Options
SNMP card
:
internal SNMP / external SNMP optional
Ⴗ
Loosen the 2 torque screws (on each side of the card).
Ⴗ
Carefully pull out the card. Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgent II-3 port is
also a tool to remotely monitor and manage any UPS system
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control
via the internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making
NetAgent II a versatile management tool. NetAgent II also supports multiple languages and is
setup for web-based auto language detection.
Typical topology of the UPS Network Management
Relay card
The card is used for providing the interface for UPS peripheral monitoring. The contact
signals can reflect UPS running status. The card is connected to peripheral monitoring devices
via DB9 female to facilitate the effective monitoring of the real-time status of UPS and timely
feedback the status to monitor when abnormal situation occurs (such as UJPS failure, mains
interruption, UPS bypass and ect.). It is installed in the intelligent slot of the UPS.