IV405E Rev.000 SIEL S.p.A.
Data di emissione: 2018-06-22
Pag. 42 di 50 + FR
≤5% with non linear load
Battery
Voltage
Standard unit:
±120Vdc (20pcs
12V9AH);
(2x20pcs 12V9AH
optional)
Long run unit :
±96V/±108V/±120
Vdc (16/18/20pcs
optional)
Standard unit: ±120Vdc (2x20pcs
12V9AH);
Long run unit Optional Voltage:
±96V/±108V/±120Vdc (16/18/20pcs
optional)
Charge Current(A)
(charge current can be
set according to battery
capacity installed)
Standard unit:
1.35A (2.7A
optional)
Long run unit:
Max. current 10A
Standard unit: 2.7A
Long run unit: Max. current 10A
Transfer Time
Utility to Battery : 0ms; Utility to bypass: 0ms
Protection
Overload
AC Mode
Load≤110%: last 60min
,
≤125%: last 10min
,
≤150%: last
1min, >150% change to bypass immediately
Bat.
Mode
Load≤110%: last 10min
,
≤125%: last 1min
,
≤150%: last
5S, >150% shut down UPS immediately
Bypass
Mode
Breaker 20A
Breaker 32A
Breaker 40A
Short Circuit
120A peak
140A peak
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS
immediately
Battery Low
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO(optional)
Shut down UPS immediately
Battery
Advanced Battery Management
Noise Suppression
Complies with EN62040-2
Alarms
Audible & Visual
Line Failure, Battery Low, Overload, System Fault
Display
Status LED & LCD
Line Mode, Bypass Mode, Battery Low, Battery Bad,
Overload & UPS Fault
Reading On the LCD
Input Voltage, Input Frequency, Output Voltage, Output
Frequency, Load Percentage, Battery Voltage & Inner
Temperature
Communication Interface
USB, RS485, Parallel (optional), Coupler dry contact,
Intelligent slot, SNMP card (optional), Relay card (optional)
Environment
Operating
Temperature
0
ഒᨺ
40
ഒ
Storage Temperature
-25
ഒᨺ
55
ഒ
Humidity
0
ᨺ
95% non condensing
Altitude
< 1500m.When>1500m,lower the rated power for use
Other
Dimensions(D×W×H )
828x250x868
Weight (Kg)
115/57
170/63
171/64
Safety Conformance
CE,EN/IEC 62040-2,EN/IEC 62040-1-1