Inspections after proper installation, prior to commissioning the plant
●
All electrical and mechanical connections are securely seated and functioning properly.
●
The motor has been assembled and aligned properly.
●
The cover sheets have been remounted correctly to ensure that the motor is cooled.
●
The operating conditions correspond to the data specified on the rating plate.
●
Any supplementary motor monitoring devices and equipment have been correctly
connected and are fully functional.
●
Appropriately configured control and speed monitoring functions ensure that the motor
cannot exceed the permissible speeds specified on the rating plate.
●
The power output elements have the proper setting conditions according to type, for
example.
–
Couplings are aligned and balanced.
–
The belt tension is properly adjusted if there is a belt drive.
–
Gear tooth flank play and gear tooth tip play as well as radial play are properly
adjusted if there is gearwheel drive.
●
The minimum insulation resistance values are maintained.
●
The grounding and equipotential bonding connections have been established correctly.
●
All fixing screws, connecting elements and electrical connections are firmly tightened.
●
The rotor can spin without coming into contact with the stator.
●
All touch protection measures for moving and live parts have been taken.
●
if the second shaft end has not been used, its feather key has been secured to prevent it
from being thrown out.
●
All external fans fitted are ready for operation and have been connected so that they
rotate in the direction specified.
●
The flow of cooling air is not impeded.
●
All brakes are operating correctly.
NOTICE
Lubricating capacity of lubricating greases
Grease loses its lubricating property over time.
After longer period of storage or standstill (> 2 years) lubricate the bearings or replace
the grease.