Document No. 129-363 
Quick Reference Guide 
May 13, 2015 

Page 2 of 3

 

Siemens Industry, Inc.

 

Normal 

 

In normal operation, no passkey or laptop is 
connected. 

 

The sensor may be set to display the 
temperature and a second important point for 
the user to monitor, called the "critical" point 
(such as setpoint, airflow or fan speed). 

 

Day operation only: Setpoints may be viewed 

and adjusted in 1° increments, using the 

 

and 

 keys. 

 

The sensor displays a sun (

) or moon (

indicating whether it is in day or night 
operation. 

 

In night operation, the override button 

 

switches the TEC to day operation for the 
length of time preset in the TEC. 

Passkey 

Insert the passkey in the sensor MMI port to: 

 

View controller point numbers, descriptions, 
values, units and status. 

 

Change or command controller point values. 

 

Set up the following display options: 

 

Turn the temperature (TEMP) display on or 
off. 

 

Select a critical point to display, if desired. 

 

Select units of measure—English or 
metric. 

   

 

Figure 2.  Inserting the Passkey. 

NOTE: 

  The Semi-Flush Mount Sensor MMI port can 

only be accessed after the front housing is 
removed. 

Laptop 

To communicate with the TEC using Datamate Base, 
Datamate Advanced, or Controller Interface Software 
(CIS), connect a computer-compatible cable (see 

Accessories

) from a laptop to the sensor MMI port at 

the bottom of the sensor. This puts the sensor in laptop 

mode, which deactivates all buttons and freezes or 
blanks the display. In this mode, the controller 
communicates only with the laptop. 

Considerations 

Point 00 (SETUP): The sensors reserve Point 00 
(SETUP) for display setup mode, but only the sensor 
recognizes this point. It does not exist in the TEC 
database. 

At the operator's terminal, Point 13 on the TEC always 
reads priority OVRD because the room sensor is 
commanding the setpoint. This is normal and cannot 
be changed if Point 14 is set to Y. 

Point 1 (ADDRESS) and Point 2 (APPLICATION) 
cannot be changed. 

Display Messages 

Message 

Meaning 

ERROR 
NO COM 

Communication with the controller is lost. 

-F, #F, °F 

If one of these three symbols displays, a 
point has failed. 

LOADING 
PT# [xx] 

The sensor is automatically loading the 
point database numbers from the controller, 
and displaying them as they load. This 
happens: (1) the first time it is connected to 
the TEC, and (2) when it is connected to 
the TEC with another application. 

PASS KEY 
ACCEPTED 

The passkey has been inserted in the MMI 
port and accepted as valid. 

Point value has been overridden by 
operator. 

TEC initial point value differs from its 
factory default value. 

Specifications 

A 10K ohm thermistor is used to detect temperature. 
The effective sensing and setpoint range is 55°F to 
95°F (13°C to 35°C). 

Operating Instructions 

Setpoint (Day Operation Only) 

1. 

Remove passkey (if present) from MMI port. 

2. 

To view the setpoint screen: Press 

 or 

3. 

To change the setpoint: Press 

 or 

4. 

To cancel changes: Press 

5. 

To exit: Press 

 or wait five seconds. 