Function Blocks
UM353-1B
April
2012
3-78
3.2.71 QHD_ - Quickset Hold
QHD_
function blocks enable a real value to be changed
on-line using the QUICKSET feature. The block is
identified by an 8-character name that will be displayed in
the QUICKSET mode. The block is configured with a
range entered as MIN SCALE and MAX SCALE to set a
usable range, and a Decimal Point Position parameter can
set the allowed precision. The hold value can not be
changed beyond the -10% to 110% value of these limits
and will change continuously as the pulser is turned. The
MAX value must always be set greater than the MIN value.
The block can also be forced to track input TV by asserting
input TC high (1).
QSCHANGE enables the block output to either update
continuously in the Quickset mode as the pulser knob is
turned or to only update the output with the value in the
numeric display when the STORE button is pressed.
When configuring the DPP (Decimal Point Position) it is important to keep the resolution to the minimum necessary
for operation changes. It will take the operator longer turning the pulser if the resolution is too high. For example,
if only 0.1% changes are needed, configure a 0-100 range as 0.0 – 100.0 and not 0.000 – 100.000.
During Hot or Warm start, the QHD will power-up in the last position during a Cold start at the -10% range value.
BLOCK DIAGRAM
O1
Pulser
HOLD
Q
uick
S
et
NAME
TV
TC
T
rack
V
ariable
T
rack
C
ommand
O
utput
1
ENG
ineering
UNITS
MIN
imum
SCALE
MAX
imum
SCALE
.
.
Rev. 2
QUICKSET HOLD
O1
O
utput
1
QUICKSET HOLD
QHD_
ESN = 000
E
S
Q
Q
uick
S
et
NAME
(S)
........... 8 ASCII Char (null)
M
A
N
T
rack
V
ariable
TV
T
rack
C
ommand
TC
MIN
imum
SCALE
(H)
...................... Real (0.00)
M I N S C A L E
E
L
A
C
S
M A X
MAX
imum
SCALE
(H)
..................... Real (100.00)
E N G U N I T S
D P P
D
ecimal
P
oint
P
osition (preferred) (S) ... 0.0.0.0.0.0 (0.00)
OR
O
utput
R
ange
E S N
E
xec.
S
eq.
N
o.
(H)
................. 001 to 250
I
I
N
N
P
P
U
U
T
T
V
C
INPUT TC
(H)
.........
loop tag.block tag.output (null)
INPUT TV
(H)
.........
loop tag.block tag.output (null)
T
T
ENG
ineering
UNITS
(S)
..... 6 ASCII Char (PRCT)
Q
uick
S
et
CHANGE
...
C
ontinuous/
S
tore (C)
Q S C H A N G E
P U
V A L U E
P
ower
U
p
VALUE
(S)
......................Real (0.00)
P
ower
U
p
LAST
(S)
....................No/Yes (YES)
P U
L A S T
Summary of Contents for 353
Page 12: ...Contents UM353 1B x April 2012 ...
Page 22: ...Introduction UM353 1B April 2012 1 10 ...
Page 30: ...Configuration Overview UM353 1B April 2012 2 8 ...
Page 122: ...Function Blocks UM353 1B April 2012 3 92 ...
Page 168: ...Data Mapping UM353 1B April 2012 6 28 ...
Page 204: ...Controller and System Test UM353 1B April 2012 9 8 ...
Page 222: ...Calibration UM353 1B April 2012 11 4 ...
Page 226: ...Circuit Description UM353 1B April 2012 12 4 ...
Page 238: ...Model Designation and Specifications UM353 1B April 2012 13 12 EC Declaration of Conformity ...
Page 240: ...Model Designation and Specifications UM353 1B April 2012 13 14 ...
Page 244: ...Abbreviations And Acronyms UM353 1B 14 4 April 2012 ...