Maintenance
UM353-1
April
2012
10-6
10.4 ERROR CODES
This section describes off-line error codes, on-line error codes, and on-line status codes. Typically, a code will
point to a failed internal assembly or a failed peripheral device. Note that a configuration error can also cause an
error code or multiple error codes to be produced. For example, an error will occur when attempting to run a
configuration that includes an I/O Expander board hardware I/O block (i.e. AINU 1, AINU2, DINU1, DINU2,
ROUT1 or ROUT2) in a controller that does not have an I/O Expander board installed.
10.4.1 Off-Line Error Codes
Off-line error messages are displayed while the 353 is powered but not running function block code and therefore
not actively controlling a process. Depending on the message, user intervention will most likely be required.
Corrective action can be initiated via the Ethernet or Modbus ports as appropriate. Parameter “SE” located at
Modbus register 40002 will contain the hexadecimal form of the error number currently displayed (e.g., ERR: 213
would be sent as $00D5). An Error message can be acknowledged over the network by writing a 0 to the Modbus
register. Messages are displayed one at a time, in order of occurrence, and a message cannot be cleared until the
error condition is corrected.
Table 10-1 Off-Line Error Codes
ERROR
CODE
DESCRIPTION CORRECTIVE
ACTION
101
Board type test
Replace Controller board.
102 DRAM
error
Replace Controller board.
103 SRAM
error
Replace Controller board.
104
Flash CRC error
Press ENTER to reset and retest controller. If error remains, replace
Controller board or reinstall firmware.
202
Constant Data CRC Test
Controller operation suspended. Press ENTER to load Controller
board default constant data.
203
Calibration Data CRC Test
Controller operation suspended. Press ENTER to load Controller
board default calibration data.
205
Database Compatibility Test
Controller operation suspended. Press ENTER to, if possible, convert
the database or load Controller board default constant data.
208
Board Compatibility Test
Install compatible Controller board.
213
Calibration Data CRC Test
Controller operation suspended. Press ENTER to load I/O Expander
board default calibration data.
214
Software Compatibility Test
Controller operation suspended. Replace I/O Expander board or press
ENTER to remove from the configuration all references to blocks
relating to the Expander board.
215
Database Compatibility Test
Controller operation suspended. Replace I/O Expander board or press
ENTER to, if possible, convert the database or load Expander board
default constant data.
216
Board Not Present
Controller operation suspended. Install I/O Expander board or press
ENTER to remove from the configuration all references to the
missing board.
218
Board Compatibility Test
Install compatible I/O Expander board.
Summary of Contents for 353
Page 12: ...Contents UM353 1B x April 2012 ...
Page 22: ...Introduction UM353 1B April 2012 1 10 ...
Page 30: ...Configuration Overview UM353 1B April 2012 2 8 ...
Page 122: ...Function Blocks UM353 1B April 2012 3 92 ...
Page 168: ...Data Mapping UM353 1B April 2012 6 28 ...
Page 204: ...Controller and System Test UM353 1B April 2012 9 8 ...
Page 222: ...Calibration UM353 1B April 2012 11 4 ...
Page 226: ...Circuit Description UM353 1B April 2012 12 4 ...
Page 238: ...Model Designation and Specifications UM353 1B April 2012 13 12 EC Declaration of Conformity ...
Page 240: ...Model Designation and Specifications UM353 1B April 2012 13 14 ...
Page 244: ...Abbreviations And Acronyms UM353 1B 14 4 April 2012 ...