51
Item
Unit
15.5 kV
27.6 kV
38.0 kV
Lightning impulse withstand voltage
Full wave 1.2/50 µs
Chopped wave 2 µs
1
Chopped wave 3 µs
kV
110
142
----
150
194
----
200
258
----
Power-frequency withstand voltage
kV
50
60
80
Rated short-circuit current
kA
20/25/31.5/40
20/25
20/25/31.5/40
%dc component
%
48
48
48
Rated (making) closing and latching current
kA
52/65/82/104
52/65
52/65/82/104
Rated duty cycle
Reclosing duty
Non-reclosing duty
----
O-0.3 s-CO-3 min.-CO
CO-15 s-CO
O-0.3 s-CO-3 min.-CO
CO-15 s-CO
O-0.3 s-CO-3 min.-CO
CO-15 s-CO
Minimum reclosing time
2
s
0.3
0.3
0.3
Rated power frequency
Hz
60
60
60
Capacitance switching
Overhead line
Isolated bank
Back-to-back
A
100
400
400
100
400
400
100
250
250
Operating temperature range
Standard
Special
°C
-30 to +40
-40 to +40
3
-30 to +40
-40 to +40
3
-30 to +40
-40 to +40
3
Operating mechanism
----
Magnetic actuator
Magnetic actuator
Magnetic actuator
Closing time
4
ms
≤55
≤55
≤55
Opening time
4
ms
≤33
≤33
≤33
Emergency manual trip (externally operable)
----
Standard
Standard
Standard
Auxiliary voltages
Close, trip and protection
Space heaters, auxiliaries
----
Vac
Refer to Table 11
120/240
Refer to Table 11
120/240
Refer to Table 11
120/240
Interrupting medium
----
Vacuum
Vacuum
Vacuum
Breaks per pole
----
1
1
1
Contact gap (stroke)
1,200 A
2,000 A
3,000 A
mm
20/25
13-15
13-15
----
31.5/40
7-9
7-9
7-9
13-15
13-15
----
18-22
18-22
----
Radio influence voltage (RIV) 1,000 kHz
μV
≤500
≤650
≤650
Seismic withstand (optional) (ANSI/IEEE 693-2005
high-response spectrum)
g
0.5
0.5
0.5
Table 13: Technical ratings
Footnotes:
1.
Circuit breaker is in closed position.
2.
User must supply external time delay (typically using setting in reclosing relay) to assure the minimum reclose time interval of 0.3 s in accordance
with ANSI/IEEE C37.06.
3.
Consult factory for -50 °C.
4.
Add 10 ms if command power is ac.