33
Equipment maximum
voltage rating kV
Equipment rated power-
frequency withstand kV
(rms)
Maximum ac rms test
voltage kV
Maximum dc test
voltage kV
15.5
50
38
53
27.6
60
45
64
38
80
60
85
Table 4: High-potential test voltages
As-found insulation and contact
resistance tests
As-found tests verify the integrity of the
circuit breaker insulation system. Megger* or
insulation resistance tests and contact-
resistance tests conducted on equipment
prior to installation provide a basis of future
comparison to detect changes in the
protection afforded by the insulation system,
and in the integrity of the current carrying
path. A permanent record of periodic as-
found tests enables the maintenance
organization to determine when corrective
actions are required by watching for
significant deterioration in insulation
resistance, or increases in contact resistance.
* Megger is a registered trademark of Megger
Group, Ltd.
Insulation and contact-resistance test
equipment
In addition to the high-potential test
equipment capable of test voltages as listed
in Table 4, the following equipment is also
required:
AC high-potential tester with test voltage
of 1,500 volts, 60 Hz
Test equipment for contact-resistance tests.