44
Circuit
breaker
type
SDV7-SE
Rated
maximum
voltage
Rated withstand
voltages
Rated
short-
circuit and
short-time
current
Rated
interrupting
time
2
Rated
continuous
current
Rated transient
recovery voltage
3
Rated
permissible
tripping
delay time
Y
Rated
closing
and
latching
current
Lightning
impulse
(BIL)
Power
frequency
u
c
TRV
peak
value
t
3
time
to
voltage
u
c
kV, rms
kV
1
kV
kA, rms
ms/cycles
A, rms
kV
μs
sec
kA, peak
15.5-20
15.5
110/142
50
20
50/3
1,200, 2,000
29.2
32
2
52
15.5-25
15.5
110/142
50
25
50/3
1,200, 2,000
29.2
32
2
65
15.5-
31.5
15.5
110/142
50
31.5
50/3
1,200, 2,000,
3,000
29.2
32
2
82
15.5-40
15.5
110/142
50
40
50/3
1,200, 2,000,
3,000
29.2
32
2
104
27.6-20
27.6
150/194
60
20
50/3
1,200, 2,000
52.1
45
2
52
27.6-25
27.6
150/194
60
25
50/3
1,200, 2,000
52.1
45
2
65
38.0-20
38.0
200/258
80
20
50/3
1,200, 2,000,
2,500
71.7
59
2
52
38.0-25
38.0
200/258
80
25
50/3
1,200, 2,000,
2,500
71.7
59
2
65
38.0-
31.5
38.0
200/258
80
31.5
50/3
1,200, 2,000,
2,500
71.7
59
2
82
38.0-40
38.0
200/258
80
40
50/3
1,200, 2,000,
2,500
71.7
59
2
104
Footnotes:
1.
First value is full-wave impulse withstand circuit breaker open or closed. Second value is chopped-wave impulse withstand, applicable only with circuit breaker closed.
2.
Standard 50 ms (3-cycle) with 48 Vdc, 125 Vdc or 250 Vdc trip voltage or capacitor trip with 83 ms (5-cycle) interrupting time optional.
3.
TRV values are in accord with IEEE C37.06-2009. TRV peak value u
c
is roughly equal to historic E
2
value in ANSI C37.06-2000. Value t
3
, time to voltage u
c
, is
approximately 1/1.138 times the T
2
value in ANSI C37.06-2000.
4.
First value is for standard 50 ms/3-cycle interrupting time. Second value is for optional 83 ms/5-cycle interrupting time (see note 1).
5.
Power requirement for second trip coil is approximately 70 W (dc) or 50 VA (ac). Power requirement for undervoltage device is approximately 20 W (dc) or 20 VA (ac).
Table 9: Technical ratings
Table 10: Control data
Type auxiliary
switch
Continuous current
A
Control circuit voltage
120 Vac
240 Vac
48 Vdc
125 Vdc
250 Vdc
Circuit breaker
auxiliary switch
10
Non-inductive circuit interrupting capacity in A
10
5
10
9.6
4.8
Inductive circuit interrupting capacity in A
6
3
10
6
3
Table 11: Interrupting capacity auxiliary switch contacts
Nominal
Range
Close coil
Trip coil
4, 5
Spring charging motor
Close V
Trip V
A
A
Amperes run (avg.)
Charging seconds
48 Vdc
36-56
28-56
11.4
30/11.4
8
10
125 Vdc
90-140
70-140
2.1
7.4/4.8
4
10
250 Vdc
180-280
140-280
2.1
9.6/4.2
2
10
120 Vac
104-127
104-127
2.0
---
6
10
240 Vac
208-254
208-254
2.0
---
3
10
Summary of Contents for 3AH35-SE Series
Page 46: ...46 Table 13 Remarks ...
Page 47: ...47 Table 13 Remarks continued ...